(Solved) Three loads are connected in parallel with a terminal voltage of 250 V(rms). Load 1 absorbs 16kW and 18 KVAR. Load 2 absorbs 10KVA with a 0.8 leading power factor. Load 3 absorbs 8kVA at a unity power factor. (a) Find the combined load impedance of the three loads. (b) Draw the power triangle of the combined load

Question:

Three loads are connected in parallel with a terminal voltage of 250 V(rms). Load 1 absorbs 16kW and 18 KVAR. Load 2 absorbs 10KVA with a 0.8 leading power factor. Load 3 absorbs 8kVA at a unity power factor. 

(a) Find the combined load impedance of the three loads. 

(b) Draw the power triangle of the combined load.


Answer:



Z = 1.7 + j0.64



Comments

Popular posts from this blog

Explain superposition theorem and use the principle of superposition to find the voltage Vo in the circuit

(Solved) An LVDT is connected to an amplifier of gain 250 the output terminals of which are connected to a 5 V voltmeter. The meter's scale can be read to 1/5th of a division and has 100 divisions in all. Given that a core displacement of 0.5 mm provides an output of 2 mV from the LVDT, find, 1. The sensitivity of the LVDT 2. The sensitivity of the whole system 3. The resolution of the instrument in centimeters

324 identical galvanic cells, each of internal resistance 9 ohm are arranged as several in series, groups of cell connected in parallel The arrangement has been laid out so that power output in an externally connected resistance of value 4 ohm is maximum. If n cells are connected in every series group that form parallel combination, then find value of n.